5.5 RESISTOR R1. This task covers removal and installation.
INITIAL SETUP
Applicable Configurations:
All but Model MHP-20-4-08
Test Equipment:
Multimeter
Special Tools:
None
Materials/Parts:
Heat-shrink Tubing
Solder
Wire Ties
Hot Air Dryer
Equipment Descriptions:
Power OFF; installed in shelter
Special Environmintal Conditions:
None
General Safety Instructions:
See WARNING page
References:
None
Troubleshooting References:
None
Personnel Required:
Refrigeration Specialist
Location/Item
Removal
Action
a.
b.
c
d.
e.
Disconnect power supply from unit.
Remove top cover from evaporator section.
Remove screws and carefully pull junction box
from frame. Use care to avoid breaking sensing
line.
Cut wire ties and pull resistor away from
transformer.
Tag and unsolder or cut leads at resistor.
Remarks
High voltage can kill.
Sensing line connects TEM-
PERATURE SELECTOR to
sensing bulb which is behind
return air louver.
Figure 5-3
5-10
|