TM 9-4120-367-14
TM 07592B-14/1
Location/Item
Removal
- Continued
Testing
Installation
Action
c.
d.
e.
f.
g.
Carefully pull the control module from the junction
box. Use care to avoid breaking sensing line.
Remove four screws in order to pull cover from
mounting frame.
Remove four screws to separate mounting plate
from mounting frame.
Remove switch, nut and washer to pull switch from
mounting plate.
Tag and pull "quick disconnects from switch termi-
nals.
Check continuity in both positions. Continuity should
be indicated.
a. See figures FO-1, FO-3, FO-5, or FO-7.
b. Push quick disconnect terminals onto switch.
Single Phase
(Mcdel F18H)
X25A16V
A1
X26A16V
B1
Blank
C1
X13A16V, X15A16V
A2
X16A16V
B2
Blank
C2
X27A20V
A3
X28A20V
B3
Blank
C3
Remarks
Sensing line connects TEM-
PERATURE SELECTOR to
sensing bulb.
If switch is to be replaced, dis-
card nut and washer (supplied
with new switch).
Figure FO-1 for F18H, figure
FO-3 for F18H-3, figure FO-5
or K1F-18H-4, figure FO-7 for
F18H-3A and F18H-4A.
5-41
5.13 EVAPORATOR FAN SWITCH S2. - Continued
Wire No.
Terminal No.
|