TM 9-4120-367-14
TM 07592B-14/1
5.17 CAPACITORS (SINGLE PHASE) C2, C3, C5. This task covers removal and installation.
lNITIAL SETUP
Applicable Configurations:
Model F18H, Single Phase
Test Equipment:
None
Special Tools:
None
Materials/Parts:
Grounding Rod
Equipment Descriptions:
Power OFF; installed in shelter
Special Environment Conditions:
None
General Safety Instructions:
See WARNING page
References:
None
Troubleshooting References:
None
Personnel Required:
Refrigeration Specialist
Location/ltem
Removal
Action
a.
b.
c
d.
e.
Disconnect power supply from air conditioner.
Remove evaporator air inlet and filter.
Ground the capacitors to discharge electrical
charge.
Tag and pull "quick disconnect" terminal from ca-
pacitor.
Remove screws, washers, and straps.
Remarks
High voltage can kill.
Use grounding rod.
Capacitor can be pulled from
frame.
5-56
|