TM 9-4120-367-14
TM 07592B-14/1
Location/Item
Cleaning
- Continued
Inspection
Installation
Action
DRY CLEANING SOLVENT (Federal Speci-
fication P-D-680) used to clean parts is
potentially dangerous to personnel and
property. Do not use near open flame or
excessive heat. Flash point of solvent is
100°F to 138°F (38°C to 59°C).
a.
b.
c.
d.
a .
b.
c.
d.
Immerse in detergent solution or dry cleaning sol-
vent (Federal Specification P-D-680).
Agitate until dirt is removed, using a soft brush if
necessary to loosen caked dirt.
Rinse in clear water or clean dry cleaning solvent.
Drain, then hold horizontal and tap each edge on
bench or floor to dislodge droplets.
Inspect for damage such as perforations or punc-
tures in the screen and aluminum.
Inspect for areas of packed or crushed material
that would obstruct airflow.
Check for deformation of the frame, and straighten
if possible without crushing aluminum.
Replace if crushed, punctured, badly deformed, or
broken.
Replace rubber insulation strip which is across top
of mist eliminator, if it is torn, partly missing,mis-
sing, or damaged.
TOP mark must be up and airflow arrows must
point outward away from coil.
Slide mist eliminator downward between the side
channels.
Replace air outlet louver.
Replace evaporator top cover.
Remarks
5.21 MIST ELIMINATOR. - Continued
e.
a.
b.
c .
d.
5-66
|