TM 9-4120-367-14
TM 07592B-14/1
Figure 1-4. Air Conditioner, Top View, Top Covers Removed, Heating Section
1.9
DIFFERENCE BETWEEN MODELS. Unless otherwise specified, all data for the F18H-3 and K1F-18H4
will also apply to the F18H-3A and K1F-18H-4A, respectively. K1F-18H4A also has the same specifications as
MHP-20-4-08.
Power Supply
Voltage
Phases
Frequency,
Hertz
*Amperes
Cooling
Heating
*Watts
CooIing
Heating
230
Single
23
20
5,200
4,400
208
3
50/60
16
12
5,000
4,400
208
3
400
26.4
15
6,500
5,200
* Conditions: 120 °F (49°C) ambient, with 90 °F (32.2°C) dry bulb, 75°F (23.9°C) wet bulb air to evaporator.
NOTE
The compressor, condenser fan motor and the evaporator blower motor are differ-
ent. They are not interchangeable because they have different windings for the
different required power supplies.
1-9
F18H
F18H-3
K1F-18H-4
50/60
|