TM  9-4120-367-14 TM 07592B-14/1 6.8  REFRIGERANT CHARGING WITH LIQUID. - Continued Location/ltem Action Remarks Charging l.    Immediately  close  HIGH  SIDE  service  valve, - Continued manifold valve and refrigerant tank valve. m.  Run the air conditioner in COOL mode with tem- perature control in extreme COOLER position for 15  minutes. n.  Check liquid sight indicator. If system is short of refrigerant, gas bubbles will appear regularly in the indicator. o.  If refrigerant system is undercharged, add addi- tional refrigerant (see paragraph 6.7’). 6-27