TM 9-4120-367-14
TM 07592 B-14/1
6.11 CONDENSER COIL. - Continued
Location/Item
Action
Remarks
Removal
c. Remove compressor.
Paragraph 6.9
- Continued
d. Unsolder tubing at joint near condenser.
Paragraph 6.3
e. Remove actuator control.
Paragraph 6.22
f. Remove condenser guard.
g. Remove four screws that secure coil to frame.
NOTE
Sight glass must be removed with
condenser coil (see paragraph 6.13).
h. Lift coil from the frame.
Installation
a. Install new drier/filter (dehydrator).
Paragraph 6.14
b. Install spring nuts on bottom of coil.
c. Position coil in air conditioner.
d. Install four screws to secure coil.
e. Install condenser guard.
f. Install and adjust Iouver control.
Paragraph 6.23
g. Solder tubing connections.
Paragraph 6.3
h. Nitrogen purge system.
Paragraph 6.5
i.
Leak test and evacuate.
Paragraphs 6.2 and 6.6
j. Charge system with liquid refrigerant.
Paragraph 6.8
k. Replace top covers.
6-40
|