TM 9-4120-367-14
TM 07592B-14/1
6.17 EVAPORATOR COIL. This task covers removal, cleaning and installation.
INITIAL SETUP
Applicable Configurations:
All
Test Equipment:
None
Special Tools:
None
Materials/Parts:
Brazing Flux
Brazing Alloy
Charging Manifold
Safety Glasses
Brazing and Soldering Set
Solvent P-D-680
Detergent Solution
Cleaning Cloths
Refrigerant R-22
Nitrogen (Cylinder)
Tools (paragraph 3.1)
Abrasive Cloth
Scale
Gloves
Equipment Descriptions:
Power OFF; removed from shelter
Special Environmental Conditions:
None
General Safety Instructions:
See WARNING page
References:
None
Troubleshooting References:
None
Personnel Required:
Direct Support
Location/Item
Removal
Action
NOTE
Remove restrictor (distributor) with
the evaporator coil.
a. Discharge the refrigerant system.
b. Remove top covers.
c. Remove evaporator air outlet louver.
d. Remove mist eliminator and brackets.
e. Remove bulb well loop clamp.
f. Unsolder tubing from evaporator coil.
Remarks
Paragraph 6.4
Paragraph 5.21
Paragraph 6.3
6-57
|