TM 9-4120-367-14
TM 07592B-14/1
6.19 ACCUMULATOR. - Continued
Location/Item
Action
Remarks
Removal
a. Release entire refrigerant charge.
Paragraph 6.4
b. Remove top covers.
c. Remove air inlet louver.
d. Remove nut and Iockwasher from stud on bottom
of accumulator.
e. Tag inlet and outlet piping. Disconnect piping.
f. Pull accumulator from frame.
Installation
a. Install new drier/filter.
Paragraph 6.14
b. Install accumulator with stud through hole in bot-
tom of evaporator compartment.
c. Install Iockwasher and nut.
d. Connect piping.
Paragraph 6.3
Inlet and outlet are imprinted with the
words Inlet, Outlet. Inlet and outlet
must be properly connected.
e. Install air inlet louver.
f. Nitrogen purge system.
Paragraph 6.5
g. Leak test and evacuate.
Paragraphs 6.2 and 6.6
h. Charge refrigerant system.
Paragraph 6.8
i.
Replace covers.
6-65
|