TM 9-4120-367-14
TM 07592B-14/1
6.23 CONDENSOR LOUVER ADJUSTMENT.- Continued
Location/item
Adjustment
(all models
except
MHP-20-4-08)
Louver
MHP-20-4-08
Louver
Replacement
Action
a.
b.
c.
d.
e.
f.
g.
h.
Before system is charged, adjust louver push-pull
control.
Close louver blades and tighten screw in me-
chanical post to lock wire on that end.
Extend actuator rod until there is a 1/4-inch
space between inner edge of mechanical post
bracket and the face of the cylinder.
Tighten the mechanical post screw.
Nitrogen purge system.
Leak test and evacuate.
Charge refrigerant system.
Replace covers.
None required.
a.
b.
c.
d.
e.
f.
N O T E
Individual louver blades are flexible
enough for removal.
Remove rear top cover.
Remove push-on type nut from louver blade to
be removed.
Bend blade to remove ends from bearings.
Remove blade.
Bend new blade in same manner as removal.
Install end bearings.
Remarks
Paragraphs 6.2 and 6.6
6-77
|