TM 9-4120-367-14
TM 07592B-14/1
6.23 CONDENDER LOUVER ADJUSTMENT. - Continued
Location/Item
Action
Remarks
Louver
g. Install push-on nut.
Replacement
Continued
CIeaning
a. Use a clean dry cloth.
b. Use detergent solution.
Adjustment (all
a. Turn off air conditioner and wait 4 hours or until
models except
air conditioner is uniformly at ambient tempera-
MHP-20-4-08)
ture or head pressure is below 150 psig (10.516
k g / cm2).
b. Remove rear top cover.
c. Loosen mechanical post screw.
d. Close condenser louvers.
e. Pull wire tight and tighten mechanical post screw.
f. Louvers must be tightly closed when air condi-
tioner is off and head pressure is below 150 psig
(10.516 kg/cm2).
Model
None required.
MHP-20-4-08
6-80
|