TM 9-4120-367-14
TM 07592B-14/1
6.26 QUECH VALVE. - Continued
Location/Item
Action
Remarks
Installation
a. Solder valve to tubing.
Paragraph 6.3
b. Install mounting bracket, two screws, spacers
and self-locking nuts.
c. Insert approximately one ounce of thermal mastic
in bulb well.
d. Insert sensing bulb of expansion valve.
e. Move bulb back and forth to distribute mastic.
f. Set bulb approximately 1 inch beyond open end.
g. Install new drier/filter.
Paragraph 6.15
h. Nitrogen purge system.
Paragraph 6.5
i.
Leak test and evacuate.
Paragraphs 6.2 and 6.6
j.
Charge system with liquid refrigerant.
Paragraph 6.8
k. Replace covers.
6-91
|