TM 9-4120-367-14
TM 0759B-14/1
[ INITIAL SETUP ]
Applicable Configurations:
All
Test Equipment:
None
Special Tools:
None
Materials/Parts:
Safety Glasses
Detergent Solution
Cleaning Cloths
Tools (paragraph 3.1)
Gloves
Equipment Descriptions:
Power OFF; installed or removed from shelter
Special Environmental Conditions:
None
General Safety Instructions:
See WARNING page
References:
None
Troubleshooting References:
None
Personnel Required:
Direct Support
Location/Item
Removal of
Assembly
Action
a.
b.
c.
d.
e.
f.
9.
Disconnect electric power to air conditioner.
Remove air inlet louver and air filter.
Disconnect condensate drain tubing.
Remove three brackets (15 and 28) above fan to
make it easier to remove fan and motor.
Remove nuts (14) and screws (26).
Remove temperature sensing bulb.
Remove four screws and Iockwashers which se-
cure fan and motor base to mounts.
Remarks
High voltage can kill.
Paragraph 5.20
Paragraph 5.24
Paragraph 5.12
6.28 EVAPORATOR BLOWER AND MOTOR. This task covers removal and installation.
6-95
|