TM 9-4120-367-14
TM 07592B-14/1
3.5 INSTALLATION OR REMOVAL.
This task covers installation, check of installation and removal.
INITIAL SETUP
Applicable Configurations:
All
Test Equipment:
None
Special Tools:
Hoist or Wrecker Sling
Materials/Parts:
Foam Insulating Material
Pressure Sensitive Tape
#10 AWG Ground Wire
Mounting Bracket
Shrims Material
Personnel Required:
Unit Maintenance (2 reqd.)
Special Environmental Conditions:
None
General Safety Instructions:
See WARNING page
References:
None
Troubleshooting References:
None
Location/Item
Shelter
Air Conditioner
a.
b.
c.
d.
e.
Select a support which allows slight slope. No
more than 5 degrees front to rear (evaporator to
condenser).
See Figure 3-1 for dimensions and location of
mounting hardware.
Leave approximately 24 inches (60.8 cm) for
maintenance.
Check that there will bean unobstructed flow of
outside air to and from condenser coil.
Check that no source of dangerous or objection-
able fumes will be within 10 feet (30.4 m) of the
fresh air intake.
Remarks
Evaporator higher than con-
denser to allow flow of con-
densate water.
Mounting hardware supplied
with unit.
More space is desirable.
Keep all sources of heat at
least 10 feet (30.4 m) from
condenser coil.
3-5
A c t i o n
|