ARMY TM 9-4210-381-14
NAVY EE-000-CA-MMA-010/7053-AC
AIR FORCE TO 35E9-136-31
4-63. CONTROL BOX - Continued.
REPAIR/REPLACE - Continued.
4.
Brace.
a.
Remove six screws (9), locknuts (4), and twelve flat washers (5) and (8).
b.
Remove control box brace (11).
c.
Place replacement brace (11) in mounting position.
d.
Install six screws (9), twelve flat washers (5) and (8), and six locknuts (4).
5.
Control Box.
a.
Tag and disconnect wiring harness wires (see Figure FO-3).
b.
Remove 10 rivets (15) securing hinge (4) to control box (13).
c.
Remove control box (13).
d.
Remove control box components listed in paragraph 4-45.
e.
Install replacement control box components listed in paragraph 4-45.
f
Install replacement control box (13) to hinge (4) with 10 rivets (15).
g.
Install left and right electric plates (para 4-30 and 4-31).
h.
Connect wiring harness wires tagged in step a (see Figure FO-3).
INSTALLATION
1.
Position control box (13) in mounting position.
2.
Install four screws (1), flat washers (2), and locknuts (3).
3.
Install bolt (20), two flat washers (19), and locknut (18).
4.
Close control box (para 4-45).
5.
Close left electric plate (para 4-30).
6.
Close right electric plate (para 4-31).
FOLLOW ON ,PROCEDURES
1.
Install center front evaporator panel (para 4-22).
2.
Connect air conditioner input power at source.
4-122
|