ARMY TM 9-4120-381-14
NAVY EE-000-CA-MMA-010/7053-AC
AIR FORCE TO 35E9-136-31
5-19.
DISCHARGING COMPRESSOR.
This task covers: Service
INITIAL SETUP:
Tools:
Tool kit, service, refrigeration unit (Item 1, Appendix B)
Gloves, chemical (Appendix C)
Goggles, industrial (Appendix C)
Personnel: 1
Equipment Conditions :
WARNING
Disconnect input power to the air conditioner before performing any internal maintenance. Voltages
used can KILL. Shutting the unit off at the control panel does not disconnect unit power.
1.
Disconnect air conditioner input power at source.
2.
Remove right front condenser panel (para 4-28).
SERVICE
WARNING
Death or serious injury may result if personnel fail to observe safety precautions. Use great care to
avoid contact with liquid refrigerant or refrigerant gas being discharged under pressure. Sudden and
irreversible tissue damage can result from freezing. Wear thermal protective gloves and a face
protector or goggles in any situation where skin-eye-contact is possible. Prevent contact of
refrigerant gas with flame or hot surfaces. Heat causes the refrigerant to break down and form
carbonyl chloride (phosgene), a highly poisonous and corrosive gas.
1.
Remove discharge and suction gauge caps.
2.
Connect service manifold high pressure hose (red) to compressor discharge valve.
3.
Connect service manifold low pressure hose (blue) to compressor suction valve.
4.
Frontseat (clockwise) compressor suction service valve.
5.
Frontseat (clockwise) compressor discharge service valve.
6.
Discharge compressor (para 5-20, steps 2-6).
7.
Remove service manifold hoses from compressor.
5-37
|