ARMY TM 9-4210-381-14
NAVY EE-000-CA-MMA-010/7053-AC
AIR FORCE TO 35E9-136-31
4-28. RIGHT FRONT CONDENSER PANEL.
This task covers:
Removal
Inspection
Repair/Replace
Installation
INITIAL SETUP:
Tools
Tool kit, service, refrigeration unit (Item 1, Appendix B)
Electric portable drill (Item 6, Appendix B)
Twist drill set (Item 7, Appendix B)
Blind riveter (Item 8, Appendix B)
Gloves, chemical (Appendix C)
Personnel: 1
Materials:
Adhesive .(Item 1, Appendix E)
Bulk gasket material
Bulk insulation material
Rags (Item 12, Appendix E)
Methyl-ethyl ketone (MEK) (Item 13, Appendix E)
Equipment Conditions:
WARNING
Disconnect input power to the air conditioner before performing any internal maintenance. Voltages
used can KILL. Shutting the unit off at the control panel does not disconnect unit power.
Disconnect air conditioner input power at source.
REMOVAL
1.
Loosen eight captive fasteners (6) (see Figure 4-32).
2.
Remove panel (1).
INSPECTION
1.
Check that panel (1) is not bent, cracked, or punctured.
2.
Check that gasket (5) and insulation (3) are not torn, loose, or missing.
3.
Check that captive fasteners (6) are not damaged or missing.
4.
Check front service valve panel for missing rivets (8) or damaged hinge (7).
5.
For removal and repair of front service valve panel refer to paragraph 4-29.
NOTE
Repair consists of replacing gasket, insulation, captive fasteners, rivets or panel.
REPAIR/REPLACE.
1.
Gasket.
a.
Remove captive fasteners.
b.
Remove damaged gasket (5) from panel (1).
4-50
|