TM 9-4120-389-14 Table 4-2.  UNIT TROUBLESHOOTING- (cont.) MALFUNCTION TEST OR INSPECTION CORRECTIVE ACTION Step 6. Check for loose electrical connections.  Tighten electrical connections. Step 7. See wiring diagram, FO-1 and check for defective wiring.  Repair wires per para.  4-36. 2. EVAPORATOR   AND   CONDENSER   FANS   BOTH   RUN,   BUT   COMPRESSOR   DOES   NOT   START AFTER TIME DELAY. Step 1. Check to see if HIGH or LOW pressure cut-out switch has tripped. Remove  access  cover  per  para.    4-17  and  push  reset  button.    If  compressor  fails  to  start, contact your supervisor and Direct Support Maintenance. 4-42