TM 9-4120-389-14
4-20. MIST ELIMINATOR
Preliminary procedure: Remove top cover (see para. 4-14).
a.
Removal.
(1)
Slide mist eliminator up and out of mist eliminator brackets.
(2)
Remove mist eliminator brackets from evaporator coil by removing two screws and flat washers.
b.
Inspection.
(1)
Check for punctures, cuts and other visible damage.
(2)
Check for packed or mashed areas that would block air flow.
(3)
Replace defective mist eliminator.
(4)
Check mist eliminator brackets for damage and loose or missing hardware.
Replace as needed.
c.
Service
(1)
Wash mist eliminator in mild detergent (Item 26, Appendix E) and water solution.
(2)
Rinse thoroughly in clean water.
(3)
Shake out excess water prior to installation.
d.
Installation.
(1)
Install mist eliminator brackets on evaporator coil with two screws and flat washers.
(2)
Slide mist eliminator straight down into brackets. Follow-on procedure: Install top cover (See para.
4-14).
4-73
|