TM 9-4120-389-14
d.
Installation
(1)
Align cover holes with mounting hardware in mounting frame while threading the capillary
tube in bottom slots of cover and frame.
CAUTION
Take care that sensing bulb capillary tube is not kinked and that
bulb and capillary tube is not damaged during installation.
(2)
Carefully thread sensor bulb and capillary tube through the slot in
the junction box while at
the same time, placing the control module in the junction box cavity.
CAUTION
Take care that sensing bulb capillary tube is not kinked and that
bulb and capillary tube is not damaged during installation.
(3)
Maneuver the control module in junction box cavity to engage P2 to J2.
(4)
Tighten jackscrew until positive engagement of P2 and J2 is achieved.
(5)
Coil capillary tube to produce 10 loops.
(6)
Install clamp on sensor bulb.
(7)
Install clamp and bulb in evaporator inlet bell with screw and washer.
(8)
Install wiring harness clamp and clamp and capillary tube loop with spacer, screw, washer
and nut.
Follow-on procedure: Install evaporator inlet louver (See para. 4-18).
4-122
|