TM 9-4120-389-14
Table 2-2. Operator Control Settings
Mode
Temperature
Fresh
Evapor-
Evaporator
Selector
Control
Air
tor
Outlet
Fabric
Mode
Switch
Thermostat
Damper
Louver
Louver
Cover
Ventilate with
VENTILATE
Does not
Closed
Open
Adjust to
Rolled up
100% recir-
operate
suit
or snapped
culated air
closed
Ventilate with
VENTILATE
Does not
Open
Open
Adjust to
Rolled up
make-up
operate
suit
and
(fresh air)
secured
Ventilate with
VENTILATE
Does no
Open
Closed
Adjust to
Rolled up
100% fresh
operate
suit
and
air
secured
Heating with
LO HEAT
Desired
Closed
Open
Slightly
Rolled up
100% recir-
or
temperature
down for
or snapped
culated air
HI HEAT
best
closed
results
Heating with
LO HEAT
Desired
Open
Closed
Slightly
Rolled up
make-up
or
temperature
down for
and
(fresh air)
HI HEAT
best
secured
results
Cooling with
COOL
Desired
Closed
Open
Slightly
Rolled up
100% recir-
temperature
up for
and
culated air
best
secured
results
Cooling with
COOL
Desired
Open
Open
Slightly
Rolled up
make-up
temperature
up for
and
(fresh air)
best
secured
results
Any mode with
Desired
Desired
Closed
Partially
Adjust to
Rolled up
make-up air
mode
temperature
and
closed
suit
and
through CBR
sealed
secured
filter
2-19
|