1
Check to see that all packing material and shipping pallet have been removed from the air
conditioner and remote control panel. Remove drain plugs or tape.
NOTE
The unit weight (less shipping pallet) is 340 pounds (166.2 kg). When lifting or moving
the unit on the shipping pallet, a forklift, or overhead lifting device may be used. When
removing the unit from the shipping pallet, or lifting the unit into position, an overhead
lifting device must be used.
2
See "INSTALLATION SITE PREPARATION" and "SHELTER REQUIREMENTS" earlier in
this work package for general information pertaining to site preparation and additional items
required for installation that are not provided with the air conditioner.
3
Check to see that power cable and remote control cable have been inserted through the air
conditioner to shelter adapter. Place them so that they will not be damaged when the air
conditioner is lifted into position. Remote control cable is not necessary if remote is installed in
air conditioner.
4
Check to see that power to air conditioner power cable has been turned off/disconnected.
5
Remove the fresh air duct and fresh air EMI screen.
6
Align mounting hardware that is used between air conditioner and mounting shelf with slotted
mounting holes. Loosely tape in place toward the front of the slotted holes.
7
Position lifting device so that lifting hook is centered over air conditioner.
WARNING
During lifting operations, the mechanic(s) must be visible to the lifting device operator
and in a position to physically guide the air conditioner as it is lifted into position.
8
Connect sling to the four outside corner air conditioner lifting rings and the lifting device.
WARNING
Do not allow anyone under equipment suspended from a lifting device. Do not allow the
unit to swing while suspended from a lifting device. Failure to observe this warning may
result in injury to personnel and damage to the equipment.
9
Carefully lift the air conditioner into position over the mounting shelf approximately 5 to 6
inches (12.7 to 15.2 cm) away from air conditioner adapter opening.
10
Connect power cable and remote control cable (if used) to connectors on front of air conditioner.