TM9 4120-423-14&P
1
Remove as much old gasket or insulation material as possible by pulling or scraping it away
from the metal surface.
WARNING
Dry Cleaning Solvent is flammable, and its vapors can be explosive. Repeated or
prolonged skin contact or inhalation of vapors can be toxic. Use a well-ventilated area,
and keep away from sparks or flame. Use goggles, gloves, and apron when appropriate.
2
Soften and remove old adhesive and gasket residue, using dry cleaning solvent and a stiff brush.
3
Minor dents and bent edges can be straightened using common sheet metal repair procedures.
Panels that are badly dented, bent, or punctured should be replaced.
4
Should touch up or refinishing be necessary, see WP0016.
5
Use only approved replacement material as specified in Chapter 8.
6
EMI gasket material specified for this unit is supplied with adhesive backing.
7
Cut gasket to size. Be sure that EMI gasket corners are mitered so that good continuous edge
contact is made.
8
Be sure that surface to which gasket is to be applied is clean and free of paint and old adhesive
material.
9
Remove backing material from adhesive side and immediately press gasket in place. Be sure
that good edge-to-edge contact is made on the EMI gaskets.
10
Cut insulation to size.
11
Be sure that the surface to which the insulation is to be applied is clean and free of paint and old
adhesive material.
12
Coat the mating surfaces of the metal and the insulation with adhesive. Let both surfaces air dry
until the adhesive is tacky but will not stick to the fingers.
13
Starting with an end, carefully attach the insulation to the metal. Press into firm contact all over.
INSTALLATION
1
Line up screw holes in access cover and air conditioner housing.
2
Using screwdriver, install cover with five screws.
3
Line up screw holes in either fresh air cover and air conditioner housing.
0024 00-3
|