Soften and remove old adhesive and gasket residue, using dry cleaning solvent and a stiff brush.
4
Use only approved replacement material as specified in Chapter 8.
5
EMI gasket material specified for this unit is supplied with adhesive backing.
6
Cut gasket to size. Be sure that EMI gasket corners are installed so that good continuous edge
contact is made.
7
Be sure that surface to which gasket is to be applied is clean and free of paint and old adhesive
material.
8
Remove backing material from adhesive side and immediately press gasket in place. Be sure
that good edge-to-edge contact is made on the EMI gaskets.
INSTALLATION
1
Place cover on box and line up holes.
2
Using screwdriver, attach the cover with six screws and lockwashers. Do not over tighten, it will
cause distortion.
3
Install evaporator section electrical module assembly. See WP0032.
4
Install evaporator top cover. See WP0026.
END OF TASK