TM9 4120-423-14&P
4
To remove P2 wiring harness, disconnect P2 connector plug at evaporator access box.
5
Using screwdriver and wrench, remove screw, nut, and clamp. (Also holds P9A harness.)
6
Tag and remove leads to terminal board TB4 and ground E3.
7
To remove P12 wiring harness, disconnect P12 connector plug from back of condenser electrical
module.
8
Tag and remove leads to terminal board TB4 and ground E3.
9
To remove P10, P11, and P13 harness, disconnect P10 connector plug from compressor.
10
Disconnect P11 connector plug from fan motor.
11
Disconnect P13 connector plug from back of condenser electrical module.
12
Tag and remove leads to terminal board TB4, switches S4 and S5, and solenoid valves L1 and
L2.
13
To remove lead S4 to S5, tag lead and remove.
REPAIR OR REPLACEMENT
1
2
See Wire List, for wire lengths and terminals information when individual wires are replaced.
INSTALLATION
1
To install P9A wiring harness, connect P9A to J9 at evaporator access box.
2
See tags, wire marking, and wiring diagram.
3
Install leads on terminal board TB4 and ground E3. Remove tags.
4
Using screwdriver and wrench, install clamp, screw and nut. (Also holds P2 harness.)
5
To install P2 wiring harness, connect P2 to J2 at evaporator access box.
6
See tags, wire marking, and wiring diagram.
7
Install leads on terminal board TB4 and ground E3. Remove tags.
8
Using screwdriver and wrench, install clamp, screw and nut. (Also holds P9A Harness.)
0047 00-3
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |