TM9-4120-423-14&P
25
Turn mode selector switch to OFF.
26
The time delay relay (K6) controls the starting time of the compressor.
27
Turn mode selector switch to COOL and temperature control to maximum COOLER.
28
Multimeter should show 25 to 31 Vdc for 15 to 60 seconds and then zero Vdc across terminals 1
and 2 of time delay relay.
29
Turn mode selector switch to OFF.
30
Disconnect power.
31
Check for loose terminal connections. Repair or replace all loose connections.
32
Check for cracks, evidence of overheating and other visible damage. Replace if damaged.
33
Connect power to air conditioner.
INSTALLATION
1
Position cover on chassis.
2
Using screwdriver and wrench, secure cover to chassis with eight screws, six locknuts and two
3
Connect P12 and P13 connector plugs to J12 and J13 connectors on back of module.
4
Carefully slip module into place and align holes.
5
Using screwdriver, secure module with eight screws.
6
Connect power.
END OF TASK
0051 00-6
|