Page Title: PURGING THE REFRIGERANT R-22 SYSTEM
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

TM9 4120-423-14&P
8
Open the nitrogen cylinder valve and adjust the regulator so that less than 1 - 2 cfm (0.028 -
0.057 cubic meters/minute) of nitrogen flows through the system.
9
Check discharge from hose attached to the low pressure charging valve to be sure that no oil is
being forced out of the system.
10
Allow nitrogen to sweep through the system at the rate of less than 1 - 2 cfm (0.028 - 0.057 cubic
meters/minute) for a minimum of 5 minutes, before starting any brazing operation. Then allow it
to continue to flow at the same rate until all brazing operations are completed.
11
After installation brazing operations are completed, allow nitrogen to flow for a minimum of 5
minutes.
12
Close nitrogen cylinder valve, nitrogen regulator, charging manifold valve, and both high and
low pressure service valves on the unit.
13
Disconnect the hose from the nitrogen tank.
14
Make sure all repairs are completed. Go to WP0072.
END OF TASK
0071 00-3