Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

TM9 4120-423-14&P
6
Close the low pressure (suction) charging manifold valve. Never introduce liquid Refrigerant R-
22 into the low-pressure (suction) service valve.
7
Position the Refrigerant-22 drum so that liquid will be used for charging. (Some drums must be
inverted and some are equipped with a selector valve.)
8
Using accurate scales measure and record the weight of the Refrigerant-22 drum.
9
Open the Refrigerant-22 drum valve.
10
Open the high-pressure service valve on the air conditioner. Allow liquid Refrigerant R-22 to
enter the system until the drum weight has decreased by 8.5 pounds (3.86 Kg) or until system
pressure has equalized.
11
Close the Refrigerant R-22 drum valve and the high-pressure (discharge) manifold valve.
12
Connect air conditioner to a remote control module assembly.
13
Connect power.
14
Turn air conditioner on and operate in the COOL mode with the TEMPERATURE CONTROL
set at the maximum COOLER position.
15
If the 6-pound (2.93 kg) full charge was obtained, skip steps 16 through 19. If the system
pressure equalized prior to obtaining a full charge of 8.5 pounds (3.86 kg) proceed with step 16.
16
Switch the Refrigerant R-22 drum to the gas only position.
17
Be sure that the Refrigerant R-22 drum has been switched to the gas position and open the
Refrigerant R-22 drum valve, the low (suction) pressure charging manifold valve and the low
(suction) pressure service valve on the air conditioner.
18
Monitor the weight of the Refrigerant R-22 drum as the air conditioner compressor pulls
additional Refrigerant R-22 gas into the system until the full 8.5-pound (3.86 kg.) charge is
obtained. When the system is fully charged, immediately close the Refrigerant R-22 drum valve
and the air conditioner low-pressure service valve.
19
Run the air conditioner in COOL mode (with TEMPERATURE CONTROL in full COOLER
position) for 15 minutes.