TEST AND INSPECTION
1
Unwrap the insulation from the evaporator coil suction line so that thermal sensing bulb is
exposed.
2
Loosen the screws and nuts in the bulb straps that attach the sensing bulb to the suction line, and
pull the bulb out of the straps. Take care to note the position (center top of suction line) of the
bulb.
CAUTION
Use care to not damage or kink the capillary.
3
Connect a remote control module and a power cable to the air conditioner.
WARNING
AC power tests must be conducted with the power on. Exercise extreme caution.
4
Turn on power to air conditioner.
5
Place the sensing bulb in a container of ice water or crushed ice so that it is reduced to a
temperature near 32Ε F (0Ε C).
6
Set the temperature thermostat control knob fully counterclockwise to COOLER position, place
one hand on the exposed suction line, and start the air conditioner in COOL mode. If a drop in
temperature is felt on the suction return line, the expansion valve is not closing fully and should
be adjusted or replaced.
CAUTION
Turn the air conditioner to OFF as soon as a definite drop in temperature is felt on the
suction return line. If the test conditions are continued more than a few seconds, the
expansion valve will fully open and an excessive flood-back of liquid Refrigerant R-22
may damage or destroy the compressor.
7
With one hand still on the suction return line, remove the sensing bulb from the container and
warm it in the other palm. If a temperature drop is not felt in the suction return line by the time
the sensing bulb no longer feels cold to the hand, the expansion valve is not opening and should
be adjusted or replaced. As soon as a temperature drop is felt, turn the air conditioner to OFF.
END OF TASK