REMOVAL
Control, Head Pressure.
1
Using screwdriver and wrench, remove the screw, lockwasher, and clamp that secures control to
the valve mounting bracket.
2
Discharge the Refrigerant R-22 system per WP0070.
3
Wrap wet rags around control body, if it is to be reinstalled.
4
While purging the system with nitrogen, debraze the tubing. (See WP0071 and WP0072).
5
Remove control from unit.
INSTALLATION
1
Position control in unit.
2
Wrap wet rags around control body.
3
While purging the system with nitrogen, braze the tubing joints.
4
Replace the dehydrator. (See WP0080).
5
Secure control to valve mounting bracket with screw, lockwasher, and clamp.