TM9-4120-423-14&P
REMOVAL
Control, Head Pressure.
1
Using screwdriver and wrench, remove the screw, lockwasher, and clamp that secures control to
the valve mounting bracket.
2
Discharge the Refrigerant R-22 system per WP0070.
3
Wrap wet rags around control body, if it is to be reinstalled.
4
5
Remove control from unit.
INSTALLATION
1
Position control in unit.
2
Wrap wet rags around control body.
3
4
Replace the dehydrator. (See WP0080).
5
Secure control to valve mounting bracket with screw, lockwasher, and clamp.
0089 00-2
|