TM9-4120-423-14&P
2
Check that metal hose, tubing and fittings are not kinked, dented, or cracked. Repair or replace
if damaged.
3
Leak test in accordance with WP0073, if leak is indicated or suspected.
REMOVAL
Flexible Hose Connection Points.
SUCTION
HOSE CONNECTION
ACCESS OPENING
HALF
COUPLING
DISCHARGE
HOSE CONNECTION
CONDENSER SUCTION
HOSE CONNECTION
CONDENSER DISCHARGE
HOSE CONNECTION
CONNECT/DISCONNECT
TYPICAL REFRIGERATION
LINE CONNECTION
NOTE
If a complete flexible hose assembly is to be replaced, it is not necessary to discharge the
Refrigerant R-22 system unless reason for replacement is a leak in hose.
1
Using wrench, loosen and disconnect hose end at evaporator assembly through access opening.
2
Using knife, cut and remove the two joined tie down straps that secure hoses to compressor
junction box.
3
Using wrench, loosen and disconnect hose end at condenser assembly located on motor
mounting bracket.
4
Carefully remove hose from air conditioner.
0091 00-2
|