TM 9-4120-428-14
0017 00
CAUTION
Do not check operation in the COOL mode until after the input power has been
reconnected to the unit for a sufficient amount of time. This is done to eliminate any
danger of liquid refrigerant accumulation in the compressor. Under moderate conditions,
if input power has been disconnected, allow for a four-hour warm-up period. If air
conditioner has been exposed to below freezing temperatures without input power, an
eight-hour warm up period is recommended.
17
1. Be sure the MODE SELECTOR switch is in the
Operational Checks
OFF position. Reconnect input power.
2. Perform function checks on the air conditioner
in all operational modes.
3. Set the air conditioner for its desired operational
mode.
4. Record the performance of quarterly PMCS,
including all corrective actions taken.
END OF WORK PACKAGE
0017 00-7
|