TM 9-4120-428-14
0025 00
INSTALLATION
To install the louver, linkage assembly, and cable:
1. Install one nut (13) 1/2 inch from each end of cable (12).
2. Insert cable (12) into retaining brackets.
3. Install nuts (13) on each end of cable (12) and tighten.
4. Install clamp (16), screw (14), and lock washer (15).
5. Slide louver assembly into unit and secure with four machine screws (8), lock washers (9), and two snap fastener studs
(10).
6. Insert the push-pull control cable wi re end through the mechanical post (1).
7. Insert end of wire through mechanical post (11) and tighten screw (11) at actuating cylinder end.
8. Close louvers and pull control cable wire (3) tight with needle nose pliers and tighten mechanical post screw (1).
NOTE
FOLLOW-ON MAINTENANCE:
Install the top-rear panel (WP 0019 00)
Install the condenser air inlet screen (WP 0025 00)
END OF WORK PACKAGE
0025 00-4
|