|
|
TM 9-4120-428-14
0071 00
CAUTION
Severe damage can affect the compressor. Never introduce liquid refrigerant into the low
pressure (suction) charging valves.
12. If the charge is still low, carefully add refrigerant.
CAUTION
Severe damage can affect the compressor. Never introduce liquid refrigerant into the low
pressure (suction) charging valves.
a)
Set the refrigerant cylinder to deliver gas only.
WARNING
The cylinder may rupture and cause personnel injury. Never introduce a high discharge
pressure into a refrigerant cylinder.
b) Ensure the pressure gauge valve is closed.
c) Open the compound gauge and charge valve s.
d) Continue to charge until the sight glass is clear and bubble-free.
e) Close the compound gauge and the charge and refrigerant cylinder valve.
13. Turn the MODE SELECTOR switch is set to OFF.
NOTE
FOLLOW-ON MAINTENANCE:
Remove service manifold (WP 0064 00)
END OF WORK PACKAGE
0071 00-5
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |