TM 5-4120-287-15 3-28.  Condenser Air Inlet Weather Cover a.     Removal.  Remove the three phillips head screws (9, fig. 3-8) securing the weather cover 8) to the air conditioner frame; then remove the weather cover. b. Inspection, Cleaning, Repair and Replacement. (1)   Perform the applicable procedures of paragraph 3-22. (2)   Replace weather cover when material thins due to weathering. (3)   Small tears may be patched with canvas until a new cover can be obtained. c. Installation.  Secure the weather cover (8, fig. 3-8) to the air conditioner frame with phillips head screws( 9) 3-29.  Condenser Right-side Access Panel Assembly a. Removal.  Loosen the panel’s twenty-eight quarter-turn fasteners by depressing fasteners and rotating one quarter- turn counterclockwise; then remove panel assembly (1, fig 3-8) from the air conditioner frame. b. Inspection, Cleaning, Repair and Replacement.  Perform the applicable procedures of paragraph 3-22. c. Installation.  Secure the panel assembly (1, fig. 3-8) to the air conditioner frame with the quarter-turn fasteners. 3-30.  Condenser Air Discharge Door Assembly a. Removal.  Remove the hinge pin (6, fig. 3-8) from the condenser door hinge.  Loosen the door’s four quarter-turn fasteners by depressing fasteners and rotating one-quarter turn counterclockwise; then remove the door (5, fig. 3-8) from the air conditioner. NOTE Do not remove condenser air discharge door assembly unless repairing or replacing door.  Sufficient access is gained to components beneath door by loosening the four quarter-turn fasteners and opening door. b. Inspection, Cleaning, Repair and Replacement. (1)   Perform the applicable procedures of paragraph 3-22. (2)   Inspect the door hinges for damage and security.  Inspect the hinge area for defective spot welds. (3)   Inspect the honeycomb assembly for damage and security. c. Installation. (1)   Secure the door (5, fig. 3-8) to the air conditioner frame with quarter-turn fasteners. (2)   Replace condenser door hinge pin (6, fig. 3-8) if it was removed. 3-13

Privacy Statement - Press Release - Copyright Information. - Contact Us - Support Integrated Publishing

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business