(8) Run leads through the grommet in the compressor junction box.
(9) See tags on the removed heater. Connect heater leads to J10 pins F and G.
(10) If this completes the repair, install terminal box cover.
d. Heater replacement (Models EKP and FGG only) (Refrigerant system discharge is not required.)
(1) Check to see that the power has been disconnected at the power source and covers have been removed
during access and testing proceeds as follows.
WARNING
Allow heater to cool before touching. Severe bums can result from touching hot
heater.
(2) Tag and disconnect two heater leads from junction box terminals.
(3) Slide heating element from tube on compressor.
(4) Install new heater as follows:
(5) Cover heating element with insulating grease and slide into tube on compressor.
(6) Run leads through the grommet in the compressor junction box.
(7) See tags on the removed heater. Connect heater leads to J10 pins F and G.
(8) If this completes the repair, install terminal box cover.
Figure 4-91.1. Compressor (Models EKP and FGG)
Change 5 4-180.1 (4-180.2 blank)