AC DOES NOT COOL OR COOLS INADEQUATELY - Continued
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
WARNING
12.
KNOWN INFO
Read WARNING on
Power to AC system OK.
AC heater/evaporator blower OK.
AC control circuits OK (except for
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
temperature control and low pressure
Is AC condenser output hose
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
switches).
hot?
AC low pressure switch OK.
No AC condenser dryer desiccant
TEST OPTIONS
contaminant in AC refrigerant system.
Visual inspection.
No AC refrigerant oil contaminant in AC
refrigerant system.
REASON FOR QUESTION
No AC system leaks.
If AC condenser output hose
Temperature control switch OK.
is hot, AC condenser is
No air or other contaminant in AC refrigerant
faulty.
system.
Go to Step 13 of this
NO
AC condenser dryer OK.
fault.
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
AC evaporator core OK.
No restricted AC hoses.
YES
AC compressor OK.
POSSIBLE PROBLEMS
Recover R-134a refrigerant
(WP 0050). Replace AC
AC condenser core faulty.
condenser core (WP 0024)
Moisture in AC refrigerant system.
and AC condenser dryer
AC expansion valve faulty.
charge system (WP 0050).
AC system overcharged.
Verify repair, go to Step 22 of
this fault.
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -