|
|
DRAFT
TB 9-2320-364-13&P-1
AC HEATER/EVAPORATOR BLOWER OPERATES BUT NO COLD AIR FROM
DUCTS DURING AC OPERATIONS - Continued
WARNING
Remove rings, bracelets, wristwatches, neck chains, and any other jewelry before working around
vehicle. Jewelry can catch on equipment and cause serious injury. Jewelry or tools may short
across electrical circuits or terminals and cause damage to equipment or severe burns or
electrical shock to personnel.
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
CONTINUITY TEST
(1) Set multimeter switch to ohms.
(2) Place positive (+) probe of multimeter on ground
wire at AC condenser motor terminal.
(3) Place negative (-) probe of multimeter on ground
wire at other end.
(a) If there is no continuity, repair AC condenser
motor ground wire (see Appendix A). Verify
repair, go to Step 29 of this fault.
(b) If there is continuity, replace AC condenser
motor (WP 0025). Verify repair, go to Step 29 of
this fault.
PLSAC198
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |