TM 10-4110-262-13&P
0023 00
INSTALL
1. Inspect the condensate drain tube in the IC rear wall and reseal the opening if necessary.
2. Inspect the seal around the perimeter of the RU back plate and, if it is serviceable, proceed to Step 3.
If the seal is not serviceable, replace it with the following procedure:
a. Remove all traces of the old seal material by cutting scraping or sanding (if necessary) both the
RU back plate and the mating surface of the IC. Be careful to avoid gouging scraping or
otherwise damaging the IC or the RU surfaces.
b. Apply a 1-in. band of adhesive around the perimeter of the RU back plate on the IC side.
c.
Remove the adhesive backing and install a replacement seal around the perimeter of the back
plate. Be careful to align the edges of the seal with the edge of the back plate.
3. Insert forklift tines into the fork pockets of the RU. Raise the forks just enough to support the RU
without lifting it.
WARNING
Personnel should wear head protection while working
below the forks of a forklift. RU mounting bolts should not
be removed until the RU is supported by a forklift. Always
use a safety strap to keep the RU on the forklift tines
during removal and installation. The RU is heavy and the
unit falling on personnel may cause serious injury or
death.
4. Attach a safety strap to the forklift and to the RU to keep the RU from falling off the forklift tines.
5. Raise the RU and move it to the opening of the IC. Align the RU evaporator (inside) section with the
opening.