Click here to make tpub.com your Home Page

Page Title: Diagnosing Using the Liquid Line
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

TM 10-4110-262-13&P
0028 00
Diagnosing Using the Liquid Line
The liquid line should be slightly warmer than the surrounding air.
1. A low refrigerant charge may cause the liquid line to be warmer than normal.
2. A liquid line restriction will cause the line to become cold after the point of restriction.
CONTROLLER DIAGNOSTICS
Before starting troubleshooting, verify that the control box 12/24 V selector is placed in the 24V position
and check the ground circuit through Pin 9 (Wire W).
NOTE
This procedure covers only control box PC board functions and does not
address all possible electrical contingencies.
PC board Diagnostic Hints
The balance of this work package is devoted to diagnostic routines designed to help the technician
quickly identify the cause of a problem and repair it using the correct tools, information and procedures.
It is important that the required procedures be followed exactly. Failure to do so may result in an
incomplete repair.
Important Diagnostic Consideration
When performing diagnostics, consider if the refrigeration system rather than the controls may cause
the problem. Diagnostic procedures for refrigeration system problems were outlined previously in this
work package.
0028 00-7

Privacy Statement - Press Release - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business