![]() TM 10-4110-262-13&P
0028 00
NOTE
Ensure Pin 9 (W) is properly grounded.
Symptom
Corrective Action
Blank display when the ON/OFF switch
Check for 24 VDC between Pin 2 (positive) and Pin 9
is pressed
(ground)
Check Fuse 4/1 located in the unit controller
Replace unit controller
Unit is not cooling when the IC interior
Check for 24 VDC between Pin 6 and Pin 9 (W)
temperature is higher than the setpoint
Check continuity on Fuse 4/1
temperature.
If no voltage, replace unit controller.
Unit operation LED is off when the unit
Check for 24 VDC on Pin 7
is cooling
Note the malfunctioning LED and continue to operate the
unit
Defrost cycle is not initiated when the
The unit must be indexed to cool (compressor on)
manual defrost switch is pressed
Evaporator coil temperature must be lower than 36 F at
the DTS.
Press the manual defrost switch and check for 24 VDC on
Pin 8.
Replace unit controller
0028 00-8
|