Symptom
Corrective Action
Defrost LED is off when the unit is in the
Check for 24 VDC between Pin 4 and Pin 2.
defrost mode
Note the malfunctioning LED and continue to operate
unit.
Run an ice bath test on the sensor. See sensor
calibration data in WP 0002 00
Temperature displayed is out of range
Check that the unit controller 12/24 V selector is in the
24 V position
Check the thermostat sensor
Unit is not working
Check overload protector LED. If on, check overload
protector.
Check F4 fuse on the printed circuit board in the RU
electrical enclosure
Check for 24 VDC between Pin 2 and Pin 9
Replace unit controller
Unit is stopped by the AC overload
Check for 24 VDC between Pin 5 and Pin 9
relay, but the AC overload LED is off
Note the malfunctioning LED and continue to operate unit.
Compressor does not run
Check for 24 VDC between Pin 6 and Pin 9
Replace controller if no power.
Unit is indexed to heat but does not run
Check for 24VDC on Pin 10 and Pin 2
If no power, replace controller.
END OF WORK PACKAGE