TM 10-4130-239-14
4-31.
ARMATURE GROUP REPLACEMENT (CONT)
3.
4.
5.
6.
7.
8.
9.
Move starter panel assembly aside.
Insert 0.010 in. (O. 254 mm) thickness gauge between armature and
flywheel with magnet directly in front of armature.
Loosen two armature mounting bolts.
Allow magnet to pull
armature down firmly against thickness gauge.
Tighten two armature mounting bolts.
Remove thickness gauge.
Install blower housing.
Install eight blower housing mounting
bolts and starter clamp.
Install. flywheel pulley.
Install two flywheel pulley mounting
bolts and two lockwashers.
4-66
|