TM 10-4130-239-14
5-17 l
CONDENSER REPLACEMENT (CONT)
1.
Remove discharge tee from condenser fitting.
2.
Remove tie wraps and insulation.
3.
Debraze copper tube at elbow fitting nearest condenser coil (para
5-4) .
4.
Remove eight plenum mounting screws and flatwashers.
5.
Remove eight condenser mounting screws, lockwashers, and
flatwashers.
6.
Lift condenser from skid base.
1.
Install new condenser on skid base and align mounting holes.
2.
Install eight condenser mounting screws, lockwashers, and
flatwashers.
3.
Install eight plenum mounting screws and flatwashers.
5-36
|