TM 10-4130-239-14
5-17.
CONDENSER REPLACEMENT (CONT)
4.
Braze copper tube onto elbow fitting (para 5-4).
5.
Tie wrap insulation over sensing bulb.
6.
Install discharge tee to condenser fitting.
7.
Install pressure relief valve (para 5-18).
8.
Replace filter-drier before evacuating system (para 5-22).
9.
Leak-test system (para 5-6).
10. Evacuate system (para 5-7).
11. Charge system (para 5-8).
5-18.
PRESSURE RELIEF VALVE REPLACEMENT.
DESCRIPTION
This task covers:
Removal and Installation
Equipment
Condition
Para
Condition Description
2-8
Engine stopped.
4-15
Housing removed.
5-3
Refrigeration system
discharged.
Tools
Tool Kit, Service
Refrigeration, item 5,
Appendix B
Materials/Parts:
Filter-drier 13226E1786
5-37
|