TM 10-4130-239-14
5-27.
THERMOSTATIC VALVE REPAIR (CONT)
1.
Remove four lower housing retaining bolts and lockwashers.
2.
Separate lower housing from upper housing.
3.
Remove seal.
4.
Remove temperature element assembly.
5.
Remove packing from temperature element assembly.
1.
Lubricate packing and seal with a light coat of grease.
2.
Install packing on new temperature element assembly.
3.
Install temperature element assembly in upper housing.
4.
Install seal in upper housing.
5.
Install lower housing on upper housing.
6.
Install four lower housing retaining bolts and lockwashers.
7.
Install thermostatic valve (para 5-26).
5-28.
START-RUN VALVE ASSEMBLY REPLACEMENT.
DESCRIPTION
This task covers:
Removal and Installation
Equipment
Condition
Para
Condition Description
Tools
2-8
Engine stopped.
Tool Kit, Service
Refrigeration, item 5,
4-15
Housing removed.
Appendix B
Tap and Die Set
5-29
Low temperature switch
(5136-01-119-0005),
removed.
item 3, Appendix B
5-66
|