|
|
TM 5-4110-217-14
CHAPTER 6
REFRIGERATION SYSTEM REPAIR
Section I. SERVICING REFRIGERATION SYSTEM
blocks above large electric light bulb If heat from other
6-1. Pumping Down.
sources is used, be sure that temperature is not raised
Before the refrigeration system can be opened for
above 175F.
maintenance, as much refrigerant as possible must be
liquefied and removed from tubing and other
6-3. Adding Refrigerant.
components and placed in the receiver tank in the
condenser compartment The procedure involved in
transferring refrigerant to the receiver tank Is known as
NOTE
pumping down To pump down the system, proceed as
Whenever available, use recycled
follows
refrigerant
for
charging
the
a Be sure that compressor suction and discharge
refrigeration system.
valves are open.
b. Close receiver outlet valve by turning valve
When refrigerant passing through sight glass
stem clockwise as far as it will go.
appears frothy during normal operation of refrigeration
c. Operate unit until suction pressure gauge
unit, the system needs additional refrigerant. A normal
registers between 0-and 1-pound per square inch
refrigerant charge consists of 14 pounds of R12 This
amount of R-12 is in the unit when shipment Is made If
d. Shut off machine and observe suction pressure
additional refrigerant is required, it indicates that a leak
gauge If pressure rebuilds appreciably, again
has developed in the system In this case, test for leak
operate machine until pressure is between 0- and
1-pound per square inch. Repeat this step until
as follows:
pressure no longer rebuilds appreciably
a. Turn stem of suction service valve
e. Close receiver inlet valve by turning valve stem
counterclockwise as far as possible
clockwise as far as it will go
b. Connect line from R-12 charging drum to the
6-2.
Opening System.
connection of compressor service valve.
Leave
connection loose at compressor suction valve and open
Before opening the refrigeration system, the
charging drum outlet valve long enough to purge all air
pressure in the system should be known If the system is
from the charging line through the loose connection.
open under high pressure, excessive loss of refrigerant
will occur; if opened under vacuum, air is drawn into the
CAUTION
equipment and causes future operating difficulties. If
Avoid bodily contact with or
pressure gauge indicates a vacuum after system has
inhaling of refrigerant gas. When in
been pumped down, cautiously open receiver outlet
an enclosed area, be sure of proper
valve enough to build a slight pressure in the system
ventilation.
Breathing
of
When a positive pressure Is assured, the part of system
Refrigerant 12 for long periods of
to be opened should be shut off from remainder of
time
could
be
injurious
to
system. Thus, If the compressor is to be removed,
personnel.
compressor suction and discharge valves should be
Tighten charging line connection at compressor suction
closed after system Is pumped down. In opening the
valve
system, observe the following precautions
c. Turn stem of suction service valve clockwise 3
a
Clean and dry equipment at the point to be
or 4 turns
opened Use a clean, lint-free cloth for this purpose.
d. Open charging drum outlet valve one or two
b. Open the necessary joints and plug and cover
turns.
opening to prevent dirt from entering.
e. Snap start switch to ON position.
c. After opening the system, do not touch internal
f. Operate unit while observing sight glass.
parts unless hands are thoroughly dry and clean.
When frothiness disappears, turn suction service valve
d.
If a spare part is to be installed, clean and dry
counterclockwise as far as It will go Allow unit to operate
the part as follows:
a while to see if sight glass remains clear If not, add
more R-12
(1) Clean the part by brushing it while
g. Close outlet valve of charging drum and back-
immersed in an approved cleaning solvent.
seat suction service valve
(2) Dry the part with heat by placing part on
Change 5 6-1
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |