TM 5-4110-217-14
Section XI. SIGHT GAUGE
6-30.
General.
(2) Remove flare nuts at liquid indicator sight
The sight gauge assembly consists of a flare fitting
gauge (83) and remove gauge.
containing a sight glass. The sight gauge is used to
b. Cleaning and Inspection.
observe liquid refrigerant as it flows through the system.
(1) Clean all parts with an approved cleaning
If the unit contains sufficient refrigerant and is operating
solvent and dry thoroughly.
normally, the sight gauge will appear clear. If insufficient
(2) Inspect sight gauge for cracks, chips, or
refrigerant is present, bubbles will show in the sight
other damage paying particular attention to the threaded
glass.
parts. Replace if defective.
c. Installation.
6-31.
Sight Gauge.
(1) Place sight gauge (83) in position and
tighten flare nuts.
a.
Removal (fig. 6-3).
(2) Refer to paragraph 6-6 and purge
(1) Refer to paragraph 6-1 and pump down
refrigeration system.
refrigeration system.
(3) Refer to paragraph 6-9 and test for leaks.
6-15
|