![]() TM 5-4110-234-14 
TO 40R7-5-7-1 
Table 2-1. 
OPERATOR PREVENTIVE MAINTENANCE 
CHECKS AND SERVICES 
INTERVAL 
Items to be 
Procedures. Check for 
For readiness 
ITEM 
Inspected 
and have repaired or 
reporting. Equip- 
NO 
B 
D 
AWM 
adjusted as necessary 
ment is not ready/ 
not available if: 
1 
* 
Panels, doors and 
Check for obstructed 
Missing panels, doors or 
screens 
screens, loose or missing 
screens, or damage that 
hardware or parts, and 
would cause operating 
obvious damage 
hazard. 
2 
* 
Wires and cables 
Inspect for cuts, broken or 
Wires are cut, broken, 
exposed wires, and loose 
loose or exposed. 
connections. 
3 
* 
Fans 
Inspect for loose set 
Set screws are loose or 
screws or bent or broken 
blades are missing or 
blades 
broken. 
Observe fans during 
Excessive vibration is 
operation for excessive 
observed. 
vibration(Do not open 
door.) 
4 
* 
Belts 
Inspect for loose, worn or 
Belts are loose, 
missing belts(1/2 inch 
excessively worn or 
(1.3 cm) defection midway 
missing. 
between pulleys.) 
5 
* 
Clutch and Idler 
Inspect for loose or 
Parts are loose or 
(F1OOOORG-2 only) 
missing parts and proper 
missing. 
belt tension. 
6 
* 
Bearings,pulleys, and 
Inspect for loose parts or 
Parts loose or damaged. 
* 
fan shaft 
obvious damage. 
7 
* 
Unit housing 
Check for cracks and 
Loose mountings, 
dents. Check for secure 
blocked drain or loose or 
mounting to wall, 
damaged seal. 
condition of seal to wall 
and proper drainage of 
condensate water, loose 
mounting or missing 
lifting fittings. 
8 
* 
Condenser and 
Inspect for dirt, dented 
Coils are in any way 
Evaporator coils 
fins or other obstructions 
obstructed for air flow. 
that would reduce air flow. 
9 
* 
Refrigeration tubing, 
Inspect for obvious leaks, 
A leak is detected or 
valves and fittings 
dented tubing 
tubing dented so as to 
interfere with flow. 
2-7 
 | 
| 
 
 Privacy Statement - Press Release - Copyright Information. - Contact Us  |