TM 5-4110-234-14
TO 40R7-5-7-1
Table 2-1.
OPERATOR PREVENTIVE MAINTENANCE
CHECKS AND SERVICES
INTERVAL
Items to be
Procedures. Check for
For readiness
ITEM
Inspected
and have repaired or
reporting. Equip-
NO
B
D
AWM
adjusted as necessary
ment is not ready/
not available if:
10
*
Inspect flywheel on
Cracked or mounting is
F10000R-6 for cracks and
loose.
loose mountings.
*
Observe compressor oil
Oil level is excessively
level (see para 2-2b(2)
high or low.
11
*
*
Engine(F10000RG-2
Check engine oil level
only)
(See para 2-2b(3), Add oil
as needed.
12
*
Fuel tank (F 1000RG-2
Inspect for leaks or
Leaks or damage that
only)
obvious damage, Add
would interfere with
gasoline as needed.
operation or create a
hazard are found.
13
*
Fuel strainer
Check sediment bowl for
Excessive dirt or other
(F10000RG-2 only)
matter in sediment bowl.
14
*
Fuel lines (F10000RG-2
Inspect for kinked lines,
Any problem is found that
only)
cuts, leaks and loose
would create a hazard or
connections
interfere with the
operation of the unit.
15
*
Gages, meters, lights
Check for loose
Parts are broken or
and switches
mountings, broken or
missing.
missing parts.
*
Observe for proper
Parts are not functioning.
indication during
operation.
16
*
Refrigerant sight glass
After 15 minutes of
Bubbles, milky flow or
operation in cooling cycle
pink color is observed.
check for bubbles or milky
flow indicating low
refrigerant charge. Check
for pink color which
indicates presence of
moisture.
17
*
*
Battery (F10000RG-2
Check water level and for
only)
loose or corroded
terminals.
18
*
Electric motor
Check for loose
(F10000R-6 only)
mountings.
2-8
|